The LCD reporting screen in the XRT1000 and above UPS’s allows much
more flexibility in communicating faults to you, and therefore has two
classes of fault messages. The first occurs when the unit is initially turned
on as explained above, and the second is if a fault is detected during
normal operation or testing.
Model XRT1000 and above error messages
LCD DISPLAY POSSIBLE CAUSE ACTION TO TAKE
Input AC Low Low AC input Verify Incoming AC
Input AC High Input AC is too high Verify Incoming AC
Input
Frequency Bad
Input AC frequency out of
range for unit.
Verify incoming freq. for this
model.
Over current Excessive output current being
drawn
Verify output load matches unit.
Check fan Fan not running Verify nothing has gotten into fan.
Over temp Fan or air passages blocked Clear air passages.
Battery Bad Battery pack is bad or
disconnected
Check battery voltage and
connections.
Hardware fault UPS has had a hardware fault Call for service
Output AC high Output voltage is too high Call for service
Output AC low Output voltage is too low Call for service
The Initial Error Message can be cleared by pressing any button. If the
fault is cleared, then the fault existed from a prior shutdown. If the fault is
not cleared then the fault presently exists. If the previous fault was due to
a low battery condition and the AC line returns to normal, the UPS will
automatically re-supply power to your equipment. In the XRT1000 and
above units, you may prevent the automatic return to power by setting the
Auto Restart to OFF in the Setup menu described earlier.